The AXV-F range of vane axial fans is designed, tested and certified to
operate at standard temperatures as well as at elevated temperatures of maximum
up to 600deg/C for 240 minutes inclusive of F600 (600deg/120mins),
F400 (400deg/120mins) and F300 (300deg/60mins) according to EN 12101-
3:2015. The following fan curves are valid for standard temperatures and
300°/60(120) minutes operation. To select a fan for 400°C/120 minutes
and 600°C/240 minutes operation, please contact our technical support.
For F600, fans come in bifurcated and belt driven configuration with motor
out of air flow.
Well suited for industrial applications, ventilation, smoke exhaust, stair case
pressurisation and for conveying clean and dusty air where medium to high
pressures are required with high airflow volume and fan efficiency.